Informational Notice: A-Feed PLC Power Supply Issue (No Service Impact)
Scheduled on 03/01/2026 18:28:00 Status In-Progress Estimated finish 08/01/2026 13:00:00Dear Customer,
This notice is to inform you of an at-risk condition identified today, 3 January 2026, relating to one of the PLC controllers associated with our A-feed switchgear.
18:28 – An issue was detected affecting the electronic power supply device serving the A-feed PLC controller.
18:35 – Engineers were on site and investigating.
18:55 – The root cause was identified as a failed electronic power supply device.
The B-feed remains stable and fully operational. As a precautionary measure, signalling from the B-feed generator has been configured to operate the A-feed, and both generators are capable of supplying the A-feed if required. The affected PLC controller also powers up correctly once generator power is present.
A replacement component has been ordered, and an engineer is scheduled to attend on Monday to install the part and return the system to normal configuration.
There is no significant risk to customer services, and this notification is issued for information purposes only.
Further confirmation will be provided once the replacement has been installed.
Kind regards,
Operations Team
Blynx AIM Ltd.